3 - 30
Chapter 3 Specifications and Functions
3.5 External circuit design
Configure up the power supply circuit and main circuit which turn off the power supply
after detection alarm occurrence and servo forced stop. When designing the main
circuit of the power supply, make sure to use a circuit breaker (MCCB).
The outline diagrams for the external device connection interface using the servo
amplifier MR-J4-GF are shown below.
(1) Example when using the forced stop of the QD77GF
CP3
+24V
24G
24VDC
Power
supply
Ready
ON
Operation
OFF
Emergency Stop
EMG
Alarm
RA1
1
FG
LG
Power Supply
Q61P
QnUCPU
PLC CPU
QD77GF
EMI
EMI.COM
Forced stop
Output module
QY41P
Yn
COM
12/24VDC
Simple Motion
module
5
INPUT
100-240VAC
7
Surge suppressor
7
7
SK
SK
SK
CC-Link IE
Field Network
R S T
CP1
3-phase
200 to 230VAC
MCCB1
EMG
MC1 to 3
MC3
MC2
MC1
RA1
CP2
+24V
24G
24VDC
Power
supply
8
8
Summary of Contents for MELSEC Q Series
Page 2: ......
Page 30: ...A 28 MEMO ...
Page 32: ...MEMO ...
Page 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Page 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Page 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Page 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Page 376: ...MEMO ...
Page 400: ...8 24 Chapter 8 HPR Control MEMO ...
Page 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Page 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Page 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Page 586: ...11 32 Chapter 11 Manual Control MEMO ...
Page 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Page 830: ...Appendix 30 Appendices MEMO ...
Page 833: ......