13 - 35
Chapter 13 Control Sub Functions
(5) During simultaneous start, a stroke limit check is carried out for the current
values of every axis to be started. Every axis will not start if an error occurs,
even if it only occurs in one axis.
[5] Setting the software stroke limit function
To use the "software stroke limit function", set the required values in the
parameters shown in the following table, and write them to the Simple Motion
module.
The set details are validated at the rising edge (OFF
ON) of the PLC READY
signal [Y0].
Setting item
Setting
value
Setting details
Factory-set
initial value
[Pr.12]
Software stroke
limit upper limit
value
Set the upper limit value of the moveable range.
2147483647
[Pr.13]
Software stroke
limit lower limit
value
Set the lower limit value of the moveable range.
–2147483648
[Pr.14]
Software stroke
limit selection
Set whether to use the "[Md.20] Feed current value" or
"[Md.21] Feed machine value" as the "current value".
0: Feed current
value
[Pr.15]
Software stroke
limit valid/invalid
setting
0:Valid
Set whether the software stroke limit is validated or
invalidated during manual control (JOG operation,
Inching operation, manual pulse generator operation).
0: Valid
:
Refer to Section 5.2 "List of parameters" for setting details.
[6] Invalidating the software stroke limit
To invalidate the software stroke limit, set the following parameters as shown,
and write them to the Simple Motion module. (Set the value within the setting
range.)
[Pr.12]
Software stroke limit
upper limit value
= [Pr.13]
Software stroke limit
lower limit value
(To invalidate only the manual operation, set "1: software stroke limit invalid" in
the "[Pr.15] Software stroke limit valid/invalid setting".)
The set details are validated at the rising edge (OFF
ON) of the PLC READY
signal [Y0].
When the unit is "degree", the software stroke limit check is not performed during
speed control (including speed control in speed-position switching control or
position-speed switching control) or during manual control, independently of the
values set in [Pr.12], [Pr.13] and [Pr.15].
REMARK
Parameters are set for each axis.
It is recommended that the parameters be set whenever possible with GX Works2.
Execution by sequence program uses many sequence programs and devices. The
execution becomes complicated, and the scan times will increase.
Summary of Contents for MELSEC Q Series
Page 2: ......
Page 30: ...A 28 MEMO ...
Page 32: ...MEMO ...
Page 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Page 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Page 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Page 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Page 376: ...MEMO ...
Page 400: ...8 24 Chapter 8 HPR Control MEMO ...
Page 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Page 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Page 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Page 586: ...11 32 Chapter 11 Manual Control MEMO ...
Page 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Page 830: ...Appendix 30 Appendices MEMO ...
Page 833: ......