5 - 28
Chapter 5 Data Used for Positioning Control
Item
Setting value, setting range
Default value
Buffer memory address
Value set with GX Works2
Value set with sequence
program
[Pr.22]
Input signal logic
selection
b0 Lower
limit
0: Negative
logic
1: Positive
logic
(Note-1):
Only the value
specified
against the
axis 1 is valid.
b0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Always "0" is set to
the part not used.
0 31+150n
b1 Upper
limit
b2 Not
used
b3 Stop
signal
b4
External
command/
switching
signal
b5 Not
used
b6
Proximity dog
signal
b7 Not
used
b8
Manual pulse
generator input
(Note-1)
b9
to
b15
Not used
[Pr.80]
External input signal
selection
1: External input signal of servo
amplifier
1
1 32+150n
2: Buffer memory of QD77GF
2
[Pr.24]
Manual pulse generator/
Incremental
synchronous encoder
input selection
0: A-phase/B-phase multiplied by 4
0
0 33
1: A-phase/B-phase multiplied by 2
1
2: A-phase/B-phase multiplied by 1
2
3: PLS/SIGN
3
[Pr.81]
Speed-position function
selection
0: Speed-position switching control
(INC mode)
0
0 34+150n
2: Speed-position switching control
(ABS mode)
2
[Pr.82]
Forced stop valid/invalid
selection
0: Valid (External input signal)
0
0 35
1: Invalid
1
n: Axis No.-1
Summary of Contents for MELSEC Q Series
Page 2: ......
Page 30: ...A 28 MEMO ...
Page 32: ...MEMO ...
Page 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Page 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Page 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Page 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Page 376: ...MEMO ...
Page 400: ...8 24 Chapter 8 HPR Control MEMO ...
Page 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Page 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Page 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Page 586: ...11 32 Chapter 11 Manual Control MEMO ...
Page 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Page 830: ...Appendix 30 Appendices MEMO ...
Page 833: ......