16 - 15
Chapter 16 Troubleshooting
Related buffer memory address
Set range
(Setting with sequence program)
Remedy
— —
Turn ON the PLC READY signal [Y0] with the BUSY signals
of all axes OFF.
— —
Do not request the start when the axis operation state is other
than "standby", "stop", and "step standby".
105 —
Review the content of the positioning or "[Pr.96] Operation
cycle setting" longer than the current setting.
78+150n
<HPR retry>
0, 1
• Validate the HPR retry function (set value: 1). (Refer to
Section 13.2.1).
• Move the work piece from the current position (on HP) using
the manual control operation (refer to Chapter 11), then carry
out a machine HPR again.
74+150n
75+150n
<HPR speed>
1 to 1000000000 [PLS/s]
1 to 2000000000 [ 10
-2
mm/min or others]
• Lower the HPR speed.
• Increase the dog signal input time.
(Refer to Section 8.2.3)
80+150n
81+150n
<Movement amount setting after proximity
dog ON>
0 to 2147483647
• Calculate the movement distance using a speed limit, HPR
speed, and deceleration time, and set the movement amount
after proximity dog ON so that the distance becomes a
deceleration distance or longer.
• Lower the HPR speed.
• Adjust the proximity dog position so that the movement
amount after proximity dog ON becomes longer. (Refer to
Section 8.2.4, 8.2.5)
74+150n
75+150n
<HPR speed>
1 to 1000000000 [PLS/s]
1 to 2000000000 [ 10
-2
mm/min]
4300+100n
<Positioning start No.>
1 to 600, 7000 to 7004, 9001 to 9004
Execute the machine HPR (positioning start No. 9001). (Refer
to Section 8.2)
4300+100n
<Positioning start No.>
1 to 600, 7000 to 7004, 9001 to 9004
Start the machine HPR (positioning start No. 9001) again.
(Refer to Section 8.2)
— —
Turn the motor more than one revolution using JOG or
positioning operation.
— —
• Execute HPR again.
• When the servo parameter "Function selection C-4 (PC17)"
is changed to "1: Not need to pass motor Z-phase after the
power supply is switched on", transfer the parameter from
the Simple Motion module to the servo amplifier and turn the
power supply of the servo amplifier OFF. Then, turn it ON
and execute HPR again.
— —
• Execute HPR again.
• Adjust the servo gain and in-position range, and execute
HPR again.
n: Axis No.-1
Summary of Contents for MELSEC Q Series
Page 2: ......
Page 30: ...A 28 MEMO ...
Page 32: ...MEMO ...
Page 97: ...3 29 Chapter 3 Specifications and Functions MEMO ...
Page 102: ...3 34 Chapter 3 Specifications and Functions MEMO ...
Page 282: ...5 162 Chapter 5 Data Used for Positioning Control MEMO ...
Page 374: ...7 16 Chapter 7 Memory Configuration and Data Process MEMO ...
Page 376: ...MEMO ...
Page 400: ...8 24 Chapter 8 HPR Control MEMO ...
Page 425: ...9 25 Chapter 9 Major Positioning Control MEMO ...
Page 528: ...9 128 Chapter 9 Major Positioning Control MEMO ...
Page 554: ...10 26 Chapter 10 High Level Positioning Control MEMO ...
Page 586: ...11 32 Chapter 11 Manual Control MEMO ...
Page 800: ...16 54 Chapter 16 Troubleshooting MEMO ...
Page 830: ...Appendix 30 Appendices MEMO ...
Page 833: ......