Output 1
10-18
MS-860 Industrial Raster Reader User’s Manual
Output Mode
(Output 1)
Pulse
Latch Mode 1 (Unlatch on Input #1)
Latch Mode 2 (Unlatch Opposite Condition)
Latch Mode 3 (Unlatch Enter Read Cycle)
NOTE: All of the Output On modes are suppressed when any Output on Warning is
active for
Output 1 (see
<K780>
command).
Definition:
Sets the condition in which the discrete output is de-activated.
Serial Cmd:
<
K810,
output on,output state,pulse width,
output mode
>
Default:
Pulse
Options:
0 = Pulse
1 = Latch Mode 1
2 = Latch Mode 2
3 = Latch Mode 3
Definition:
This is the default mode of operation in which the programmable output
is activated when the
Output On condition has been met and held active
for the duration of the selected pulse width.
Definition:
The programmable output goes active when the
Output On condition is
met and will remain active until the state of input #1 changes from inac-
tive to active.
Important
: To unlatch using the EZ Button the button’s status must be
set to unlatch mode. (See
"Unlatch Outputs"
on page 3-6.)
Definition:
The programmable output goes active when the
Output On condition is
met and will remain active until the opposite condition selected under
Output On occurs.
For example, if
Noread is enabled under Output On, the programmable
output will go active upon a noread and remain active until the opposite
condition, a good read, occurs.
Definition:
The programmable output goes active when the
Output On condition
has been met and is held active until a new read cycle begins.