To configure the Power On Macro Setting
1. On the GLOBAL SETTINGS menu click
Power on Macro Setting
. The Power On Macro Setting
dialog appears.
2. In the PLC/Controller Address area, select either
bit
for coils, or
value
for registers.
3. In the
PLC/Controller Address
frame, enter the
PLC register address,
or click the PLC/Controller
address button
to display the address dialog box.
4. Click the pull-down box to select the
target PLC memory area.
Use the numeric keypad to enter the
specific
PLC memory address.
Select the
PLC Network Address
(if applicable) and enter the specific
HMI communications port.
Click
Enter
to go back to prior dialog box.
5. If bit was selected in the PLC/Controller Address area, in the Bit Setting area, select either
ON
to set
the bit/coil or
OFF
to reset the bit/coil.
6. If the value was selected in the PLC/Controller Address area, in the Value Display Setting area, select
the
Format Unsigned, Signed, Hexadecimal
, or
BCD
from the Format drop down menu; and the Size
16
or
32
bits from the Size drop down menu; and enter the value of the constant to be written to the
register in the Set Value frame.
7. In the time Interval area, select the time
500
,
1000, 1500
, or
2000
ms from the drop down menu.
8. Click
Set
to accept changes,
Close
to cancel any changes made, or Cancel Set to cancel a previously
set Power On Macro Setting.
1010-0300, Rev 02
Basic Operation of the BLU300
61