Automatically notify support
Yes
Alert Category
Warning - Memory
SNMP Trap ID
43
CIM Information
Prefix:
PLAT
ID:
0144
User Response
Note: Each time you install or remove a DIMM, you must disconnect the server from the power
source; then, wait 10 seconds before restarting the server.
1. Refer to TIP H212293 for minimum code level.
2. Check the Lenovo support website for an applicable retain tip or firmware update that applies
to this memory error.
3. Swap the affected DIMMs (as indicated by the error LEDs on the system board or the event
logs) to a different memory channel or microprocessor.
4. If the error still occurs on the same DIMM, replace the affected DIMM.
5. (Trained technician only) If the problem occurs on the same DIMM connector, check the DIMM
connector. If the connector contains any foreign material or is damaged, replace the system
board.
6. (Trained technician only) Remove the affected microprocessor and check the microprocessor
socket pins for any damaged pins. If damage is found, replace the system board.
7. (Trained technician only) Replace the affected microprocessor.
One of the DIMMs :
•
806f050d-0400ffff : Array [ComputerSystemElementName] is in critical condition. (Drive 0)
This message is for the use case when an implementation has detected that an Array is Critical.
May also be shown as 806f050d0400ffff or 0x806f050d0400ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Hard Disk drive
SNMP Trap ID
5
CIM Information
Prefix:
PLAT
ID:
0174
User Response
Appendix A. Integrated management module 2.1 (IMM2.1) error messages
611
Summary of Contents for System x3550 M5
Page 1: ...Lenovo System x3550 M5 Installation and Service Guide Machine Type 8869 ...
Page 6: ...iv Lenovo System x3550 M5 Installation and Service Guide ...
Page 66: ...52 Lenovo System x3550 M5 Installation and Service Guide ...
Page 298: ...284 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1120: ...1106 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1124: ...1110 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1132: ...Taiwan BSMI RoHS declaration 1118 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1134: ...1120 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1142: ...1128 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1143: ......
Page 1144: ......