5. Replace the fans. (n = fan number)
•
800b010a-1e82ffff : Redundancy Lost for [RedundancySetElementName] has asserted. (Fan
Zone 2)
This message is for the use case when Redundancy Lost has asserted.
May also be shown as 800b010a1e82ffff or 0x800b010a1e82ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Fan Failure
SNMP Trap ID
11
CIM Information
Prefix:
PLAT
ID:
0802
User Response
1. Make sure that the connectors on fan n are not damaged.
2. Make sure that the fan n connectors on the system board are not damaged.
3. Make sure that the fans are correctly installed.
4.
Reseat the fans.
5. Replace the fans. (n = fan number)
•
800b010c-2581ffff : Redundancy Lost for [RedundancySetElementName] has asserted. (Backup
Memory)
This message is for the use case when Redundancy Lost has asserted.
May also be shown as 800b010c2581ffff or 0x800b010c2581ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Memory
464
Lenovo System x3550 M5 Installation and Service Guide
Summary of Contents for System x3550 M5
Page 1: ...Lenovo System x3550 M5 Installation and Service Guide Machine Type 8869 ...
Page 6: ...iv Lenovo System x3550 M5 Installation and Service Guide ...
Page 66: ...52 Lenovo System x3550 M5 Installation and Service Guide ...
Page 298: ...284 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1120: ...1106 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1124: ...1110 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1132: ...Taiwan BSMI RoHS declaration 1118 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1134: ...1120 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1142: ...1128 Lenovo System x3550 M5 Installation and Service Guide ...
Page 1143: ......
Page 1144: ......