193
XtrapulsPac - User Guide
Chapter 3 – Reference
Virtual Inputs/Outputs
Index 0x3059
Name Virtual
Inputs/Outputs
Object Code
ARRAY
Object Class
all
Number of Elements
2
Value Description
Sub Index
1
Description Virtual
Inputs
Data Type
Unsigned16
Access rw
PDO Mapping
Yes
Default Value
No
The Pac drive has 5 virtual inputs IN6 to IN10 (bit 5 to bit 9).
These virtual inputs can be connected to drive function with object 0x3050 in the same manner as for a physical
input.
Sub Index
2
Description Virtual
Outputs
Data Type
Unsigned16
Access ro
PDO Mapping
Yes
Default Value
0
The Pac drive has 3 virtual outputs OUT4 to OUT6 (bit 3 to bit 5).
These virtual outputs can be connected to drive signal with object 0x3054 in the same manner as for a physical
output.
Sub Index
3
Description Virtual
link.
Data Type
Unsigned16
Access rw
PDO Mapping
No
Default Value
0
This parameter allows connecting the virtual outputs to the virtual inputs.
bit Function
0..2 reserved
3 0
no
connection
1
connect OUT4 to IN6
4 0
no
connection
1
connect OUT5 to IN7
5 0
no
connection
1
connect OUT6 to IN8
6..15 reserved
Example: Make a controlled stop when power supply is down.
-
Define the undervoltage warning level (above the under-voltage fault). This is used to notify when power
supply is down.
-
Connect the undervoltage warning bit to OUT4
0x3054,4 = 0x30240013
-
Connect OUT4 to IN6
0x3059,3 = 8
-
Connect IN6 to INHIBIT signal
0x3051,6 = 0x60FD0003
-
Define an appropriate stop for the INHIBIT signal