165
XtrapulsPac - User Guide
Chapter 3 – Reference
Bit Name Description
0-1 SELECT_INP
Inputs
Selection:
0
Inputs from Encoder connector (differential line driver inputs)
A+/A-
->
A or PULSE
B+/B-
->
B or DIR
1
Inputs from I/O connector (logic opto-coupler inputs)
IN5
->
A or PULSE
IN3
->
B or DIR
2
Inputs from Hall Effect Sensor (Encoder connector)
Hall U ->
A or PULSE
Hall V ->
B or DIR
2
Reserved. Must be 0.
3
CNT_MODE Inputs Count Mode:
0
Quadrature (A/B) inputs
1 Pulse/Dir
inputs
4
PULSE_POL PULSE or A polarity
5
DIR_POL
DIR or B polarity
6
Reserved. Must be 0.
7
PULSE_DBL Pulse Count Mode (only for PULSE/DIR input)
0
Simple count. Count on rising edge of PULSE
Motor Speed (rpm)=60 * Pulse_Frequency / User position scaling (0x6093-2)
1
Double count. Count on rising edge and falling edge of PULSE
Motor Speed (rpm)=120 * Pulse_Frequency / User position scaling (0x6093-2)
8 COUNT_ENA
Count
Enable
11
FILTER_ENA Low pass filter:
0 Filter
disabled
1
Filter enabled (see 0x3683 for the cut-off frequency setting)
others
Reserved. Must be 0.
Sub Index
4
Description PULSE_CNT
timeout
Data Type
Unsigned16
Access rw
PDO Mapping
No
Unit ms
Default value
10
This parameter defines the timeout after the last pulse the signal PULSE_DIR will be reset.