Field Settings from Remote Controller
SiUS341802E
97
Field Settings and Test Operation
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however cannot
be checked except in the individual mode for those in parentheses.
∗
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the
indoor unit is not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote
controller is resetting when returning to the normal mode.
∗
5. If the setting mode to “Equipped”, energy recovery ventilator fan conducts the fan residual
operation by linking to indoor unit.
∗
6. Only for FXTQ-TA models
∗
7. Only for FXTQ-TA, FXDQ-M models
∗
8. If the airflow setting when thermostat is OFF is set to OFF (12(22)-3-03, 12(22)-6-03), the air in
the indoor unit will be stagnant and suction air thermistor may not detect room temperature
correctly, resulting in problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10(20)-2 to
03
(only
remote controller thermistor).
∗
9. Only for FXFQ-T and FXUQ-P sensing models
Mode
No.
(
∗
2)
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
13(23)
0
Setting of airflow rate
Standard
High ceiling 1
High ceiling 2
—
1
Airflow direction setting
(Set when a blocking pad kit has been installed.)
F (4 directions)
T (3 directions)
W
(2 directions)
—
2
Swing pattern settings
All direction
synchronized swing
—
Facing swing
—
3
Operation of downward flow flap
Equipped
Not equipped
—
—
4
Setting of airflow direction adjustment range
Draft prevention
Standard
Ceiling soiling
prevention
—
5
Setting of static pressure selection
Standard
High static pressure
—
—
6
External static pressure settings
Refer to page 108 for details.
14
(24)
4 (*6)
Optional kit setting (UV lamp + humi
economizer)
Refer to page 109 for details.
5 (*6)
Residential dry
Set temperature:
room temperature
Set temperature:
same as cooling set
temperature
—
—
15(25)
0
Drain pump operation settings
—
ON
OFF
—
1
Humidification when heating thermostat is OFF
Not equipped
Equipped
—
—
2
Setting of direct duct connection
(when the indoor unit and energy recovery
ventilator unit are connected by duct directly.)
(
∗
5)
Without direct duct
connection
With direct duct
connection
—
—
3
Interlocked operation between humidifier and
drain pump
Not interlocked
Interlocked
—
—
5
Individual setting of ventilation
Not individual
Individual
—
—
1b
3
Display of contact center
Displayed
Not displayed
—
—
4
Display of error codes on the remote controller
—
Two-digit display
—
Four-digit
display
12
Key-lock pattern settings
No operation
allowed (Cancel
procedure is
displayed.)
No operation
allowed (Cancel
procedure is not
displayed.)
No menu
operation is
allowed
(Cancel
procedure is
displayed.)
No menu
operation is
allowed any
time.
14
Setting "restricted / permitted" of airflow block
Refer to page 111 for details.
1c
0
Room temperature display
Not displayed
Displayed
—
—
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...