Troubleshooting by Error Code
SiUS341802E
195
Service Diagnosis
2.20 Blower Motor HP Mismatch
Error Code
C6-01
Applicable
Models
FXTQ-TA
Outline
Error is issued if the manufacturer ID and output of the connected fan motor do not match those
recognized by the indoor unit.
Error Decision
Conditions
Gathers information on the manufacturer ID and output of the fan motor when initializing the fan
motor.
If those figures are not the values recognized by the indoor unit, it will be deemed abnormal
operation.
If deemed abnormal operation, it will keep retrying until the figures match.
Error Reset
Conditions
If the manufacturer ID and output match, the error will be cleared.
Supposed
Causes
Incorrect size motor
Indoor unit capacity setting error
Corrective
Actions
Correct motor installation.
Correct the indoor unit capacity setting.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...