Protection Control
SiUS341802E
57
Functions and Control
6.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
Normal Operation
3-step down
9-step up
9-step down
3-step up
21-step down
After 30 seconds
After 20 seconds
After 20 seconds
After 30 seconds
A
(˚C) >
X
(˚C)
(
A
(˚F) >
Y
(˚F))
A
(˚C) <
X
–10
(˚C)
(
A
(˚F) <
Y
–18
(˚F))
A
(˚C) >
X
+5
(˚C)
(
A
(˚F) >
Y
+9
(˚F))
A
(˚C) <
X
–5
(˚C)
(
A
(˚F) <
Y
–9
(˚F))
A
(˚C) >
X
+10
(˚C)
(
A
(˚F) >
Y
+18
(˚F))
A
(˚C) >
X
+15
(˚C)
(
A
(˚F) >
Y
+27
(˚F))
A
(˚C) >
X
(˚C)
(
A
(˚F) >
Y
(˚F))
Compressor step: 1
After 20 seconds
HTdi > 135˚C (275˚F)
HTdi > 120˚C (248˚F)
continues for 10 minutes
Ti > 120˚C (248˚F)
continues for 5 seconds
Ti > 115˚C (239˚F)
continues for 10 minutes
OR
HTdi
: Value of inverter compressor discharge pipe temperature (Tdi) compensated with outdoor air temperature
Ti
: Compressor body temperature
A
: Maximum of HTdi and Ti
X(˚C)(Y(˚F)):
RXLQ72TA, RXYQ72-120TA
→
115˚C (239˚F) (constant)
RXLQ96/120TA, RXYQ144/168TA
→
Temperature determined by compressor rotation speed
Upper limit compressor step:
max (Max. Step)
Current
step
maintained
Discharge pipe temperature standby
(3 times within 100 minutes)
Abnormal stop
(
F3
is displayed)
Discharge pipe temperature
standby
(2 times within 100 minutes)
After 30
seconds
100
105
110
X (˚C)
212
221
230
80 90
120
Y (˚F)
Compressor
rotation speed (rps)
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...