SiUS341802E
Check
Service Diagnosis
288
RXLQ72TAYDU
Point of Measurement and Judgement Criteria
Turn OFF the power supply. Then, after a lapse of 10 minutes or more, make measurement of
resistance.
PCB and Circuit Diagram
When using the analog type of multimeter,
make measurement in resistance
measurement mode in the x1 k
Ω
range.
When using the digital type of multimeter,
make measurement in diode check mode
(
)
No.
Measuring
point
Judgement
criteria
Remarks
No.
Measuring
point
Judgement
criteria
Remarks
+
–
+
–
1
P21
U
2 ~ 30 k
Ω
1
P21
U
1.2 V or
more
Due to condenser
charge and so on,
resistance
measurement may
require some time.
2
P21
V
2
P21
V
3
P21
W
3
P21
W
4
U
P21
15 k
Ω
or
more
(including
)
Due to condenser
charge and so on,
resistance
measurement may
require some time.
4
U
P21
0.3 ~ 0.7 V
5
V
P21
5
V
P21
6
W
P21
6
W
P21
7
N5
U
7
N5
U
8
N5
V
8
N5
V
9
N5
W
9
N5
W
10
U
N5
2 ~ 30 k
Ω
10
U
N5
1.2 V or
more
Due to condenser
charge and so on,
resistance
measurement may
require some time.
11
V
N5
11
V
N5
12
W
N5
12
W
N5
R867
V2R
C47
X41A
C48
HAP
+
P11
X601A
BLK
X2A
N5
X5A
X4A
–
F601U
+
RED
+
L11
WHT
L12
+
PS
K3R
L3B
L2B
V
R865
P4
X602A
N4
X63A
K1M
–
P5
U
V1R
L1B
R313
P21
W
X6A
460V 16K
U
V
W
N5
P21
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...