SiUS341802E
Refrigerant Circuit
Refrigerant Circuit
14
1.2
Indoor Unit
∗
1. R1T is for remote controller thermistor or optional remote sensor.
No. in piping
diagram
Name
Symbol
Function
Except
FXMQ-PB,
FXTQ-TA
FXMQ-PB
FXTQ-TA
(1)
Electronic expansion
valve
Y1E
Y1E
Y1E
Used for gas superheated degree control while
in cooling or subcooled degree control while in
heating.
(2)
Suction air thermistor
R1T
R1T
R1T (
∗
1)
Used for thermostat control.
(3)
Liquid pipe thermistor
R2T
R2T
R2T
Used for gas superheated degree control while
in cooling or subcooled degree control while in
heating.
(4)
Gas pipe thermistor
R3T
R3T
R3T
Used for gas superheated degree control while
in cooling.
(5)
Discharge air thermistor
—
R4T
—
Used for discharge air temperature control.
FXFQ-T, FXFQ-P, FXHQ-M
FXZQ-TA
FXZQ-M
FXUQ-P, FXEQ-P, FXSQ-TA, FXMQ-M, FXAQ-P,
FXLQ-M, FXNQ-M
C: 4D024460P
(4)
(3)
Indoor heat exchanger
Fan
Filter
Filter
(1)
Gas piping
connection port
Liquid piping
connection port
(2)
(4)
(3)
(1)
(2)
C: 4D110602
Indoor heat exchanger
Fan
Filter
Filter
(4)
(2)
(1)
(3)
Gas piping
connection port
Liquid piping
connection port
C: 4D040157B
Indoor heat exchanger
Fan
Filter
Filter
(4)
(2)
(1)
(3)
Gas piping
connection port
Liquid piping
connection port
C: 4D034245R
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...