Troubleshooting by Error Code
SiUS341802E
249
Service Diagnosis
2.53 Reactor Surface Thermistor Abnormality
Error Code
P3
Applicable
Models
RXLQ72TATJU
Method of Error
Detection
Detect according to the value detected with the reactor surface thermistors.
Error Decision
Conditions
When the system is in operation and the thermistor disconnection or short circuit is detected.
Supposed
Causes
Defective connection of thermistor
Defective reactor surface thermistor(s)
Defective inverter PCB
Troubleshooting
Disconnect the thermistors
from the inverter PCB (A3P),
and check the resistance.
NO
YES
YES
NO
Correct the connection.
NO
Replace the defective
thermistor(s).
YES
Replace the inverter PCB
(A3P).
Continue operation.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the
thermistors
(R71T, R72T) correctly
attached to the
PCB ?
Turn ON
the power supply,
and check if the
P3
error
recurs when
operation
starts.
Are the
resistance of the
thermistors
normal?