Troubleshooting by Error Code
SiUS341802E
169
Service Diagnosis
2.2
Indoor Unit PCB Abnormality
Error Code
A1
Applicable
Models
All indoor unit models
Method of Error
Detection
Check data from EEPROM.
Error Decision
Conditions
When data could not be correctly received from the EEPROM
EEPROM : Type of nonvolatile memory. Maintains memory contents even when the power supply
is turned OFF.
Supposed
Causes
Defective indoor unit PCB
External factor (Noise etc.)
Troubleshooting
Turn the power supply OFF,
then the power ON again.
Does the
system return to
normal?
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the indoor unit main
PCB (A1P).
The indoor unit main PCB
(A1P) is normal.
External factor other than
error (for example, noise
etc.).
NO