Troubleshooting by Error Code
SiUS341802E
255
Service Diagnosis
2.57.2 Reverse Phase, Open Phase (RXLQ72TAYDU)
Error Code
U1
Applicable
Models
RXLQ72TAYDU
Method of Error
Detection
The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.
Error Decision
Conditions
When a power supply is reverse phase, or T phase is open phase.
Supposed
Causes
Power supply reverse phase
T phase open phase
Defective outdoor unit main PCB (A1P)
Troubleshooting
There
is an open
phase at the power
supply (T phase) terminal
section (X1M) of the
outdoor unit.
Operation
is normal if one
phase of power supply
line phase is
replaced.
Faulty wiring or
wiring disconnection
between the outdoor unit
main PCB (A1P) and the
open phase
protection PCB
(A10P)?
Fix the open phase. Requires
inspection of field power supply
section.
Reverse phase.
Countermeasure of the problem is
completed by phase replacement.
Correct the falty wiring or the
wiring disconnection.
YES
YES
YES
NO
NO
Replace the outdoor unit main
PCB (A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...