SiUS341802E
Check
Service Diagnosis
290
RXLQ72-120TAYCU, RXYQ72-168TAYCU
Point of Measurement and Judgement Criteria
Turn OFF the power supply. Then, after a lapse of 10 minutes or more, make measurement of
resistance.
PCB and Circuit Diagram
When using the analog type of multimeter,
make measurement in resistance
measurement mode in the x1 k
Ω
range.
When using the digital type of multimeter,
make measurement in diode check mode
(
)
No.
Measuring
point
Judgement
criteria
Remarks
No.
Measuring
point
Judgement
criteria
Remarks
+
–
+
–
1
P31
U
2 ~ 30 k
Ω
1
P31
U
1.2 V or
more
Due to condenser
charge and so on,
resistance
measurement may
require some time.
2
P31
V
2
P31
V
3
P31
W
3
P31
W
4
U
P31
15 k
Ω
or
more
(including
)
Due to condenser
charge and so on,
resistance
measurement may
require some time.
4
U
P31
0.3 ~ 0.7 V
5
V
P31
5
V
P31
6
W
P31
6
W
P31
7
N31
U
7
N31
U
8
N31
V
8
N31
V
9
N31
W
9
N31
W
10
U
N31
2 ~ 30 k
Ω
10
U
N31
1.2 V or
more
Due to condenser
charge and so on,
resistance
measurement may
require some time.
11
V
N31
11
V
N31
12
W
N31
12
W
N31
P11
P21
IGBT
U
V
W
L1B
L2B
L3B
DM
P31
N31
P31
U
V
W
N31
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...