Field Setting from Outdoor Unit
SiUS341802E
127
Field Settings and Test Operation
Next time graph shows the different steps during the power transistor check mode.
Switching sequence during power transistor check mode:
Check 1 :
AC power input (connector X10A on A2P: inverter compressor) 380-415 V unbalance max.2%.
Check 2 :
relay “K1M” on inverter PCB switches: check DC voltage on P&N increase to ±500 VDC.
Check 3 :
DC = 1.42 x VAC power supply L1-L3: check at the points below.
Check 4 :
AC UVW 10 Hz intermediate: check difference within 10 V (at fasten UVW)
Check 5 :
AC UVW 240 Hz continuous output while voltage drop (discharge capacitors DC) check
difference between UVW within 10 V. 2 LEDs (V phase) brightness reduce until OFF.
*Note: Actual voltage value depends on meter characteristics
[2-29]: Capacity priority
When the night-time low noise operation is in use, performance of system might drop because airflow rate
of outdoor unit is reduced.
Default value: 0. Capacity priority cannot be used.
Field setting 1: Capacity priority can temporary cancel the night-time low noise operation. Capacity priority
can be initiated when certain operation parameters approach the safety setting:
Raise in high pressure during cooling.
Drop in low pressure during heating.
Raise of discharge pipe temperature.
Raise of inverter current.
Raise of fin temperature inverter PCB.
Frequency: 240 Hz
±30 sec
±3 sec
Magnectic
switch
K1M OFF
Voltage
output
UVW
±170
VAC*
Check 3
±6 sec
±3 sec
Check 5
±60 VAC*
Check 2
Check 1
±100V
AC*
Step 2:
Mode
2-28
Set 02
Ѝ
01, then
press “Return” twice
OR press “MODE” button
Voltage
output
UVW
Check 4
Frequency: 10 Hz
Step 1:
Mode 2-28
Set 01
Ѝ
02, then
press
“Return” twice
Magnectic
switch (K1M)
ON
Disconnect UVW from compressor before
performing the power transistor check.
(5) In case of RXLQ96/120TATJU
C+
C-
Opening hole
+
-
Multimeter
(3)
(4)
(5)
(1)
(2)
Multimeter
+
-
(White connector)
(4) In case of RXLQ72TAYDU
(2) In case of RXLQ96/120TAYDU
(3) In case of RXLQ · RXYQ-TAYCU
(1) In case of RXLQ72TATJU
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...