Field Setting from Outdoor Unit
SiUS341802E
133
Field Settings and Test Operation
[2-60]: Gas furnace setting
Default value: 0.
When a gas furnace is connected, the setting [2-60] has to be changed to 1.
[2-78]: Heat pump lockout temperature
Heat pump is locked out when the outdoor air temperature is smaller than the heat pump lockout
temperature.
This is only effective when the heat pump lockout 2 setting [2-37] is Mode 3 to 6.
[2-79]: Heat pump lockout release differential
Heat pump is resumed when the outdoor air temperature is recovered by differential above the heat
pump lockout temperature.
[2-81]: Cooling comfort setting
This setting is used in conjunction with setting [2-8].
[2-82]: Heating comfort setting
This setting is used in conjunction with setting [2-9].
Value
[2-78]
Heat pump lockout temperature
0 (default)
–26.1°C (–15°F)
1
–23.3°C (–10°F)
2
–20.5°C (–5°F)
3
–17.7°C (0°F)
4
–15°C (5°F)
5
–12.2°C (10°F)
6
–9.4°C (15°F)
7
–6.6°C (20°F)
8
–3.8°C (25°F)
9
–1.1°C (30°F)
10
1.6°C (35°F)
11
4.4°C (40°F)
12
7.2°C (45°F)
13
10°C (50°F)
14
Forced heat pump lockout
Value
[2-79]
Heat pump lockout release differential
0
2.8°C (5°F)
1 (default)
5.6°C (10°F)
2
8.3°C (15°F)
Value
[2-81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
Value
[2-82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...