SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
184
Model
∗
1: Swing motor connector
∗
2: Swing motor
FXFQ-T
X9A
M1S, M2S, M3S, M4S
FXFQ-P
X36A
M1S
FXZQ-TA
X105A
M1S
(with decoration panel BYFQ60B)
M1S, M2S, M3S, M4S
(with decoration panel BYFQ60C)
FXZQ-M
X28A
M1S
FXUQ-P
X36A
M1S, M2S, M3S, M4S
FXEQ-P
X36A
M1S, M2S, M3S, M4S
FXHQ-M
X6A
M1S
FXAQ-P
X36A
M1S
Replace the power supply
relay cable.
Replace the defective
swing motor. (
∗
2)
Take the flap-cam mechanism
apart, reassemble and turn ON
again.
YES
NO
YES
NO
The relay cable has no
continuity.
When
the airflow
direction flap-cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned ON
again.
A