Troubleshooting by Error Code
SiUS341802E
177
Service Diagnosis
Troubleshooting
The
fan motor
connectors (X1A
and X2A) of the fan
PCB (A2P) are
disconnected.
Remove the foreign matter.
YES
Connect the connector correctly.
YES
NO
The
connectors
between the
indoor unit PCB (A1P)
and the fan PCB (A2P)
are disconnected.
Connect the connector correctly.
YES
NO
The
fuse (F3U,
white) on the fan PCB
(A2P) has no
continuity.
Replace the fan PCB (A2P).
NO
Replace the indoor fan motor (M1F).
YES
NO
YES
The
fan can
be moved
lightly by hand after
the fan motor connector
of the fan PCB
(A2P) is
removed.
Replace the indoor fan motor (M1F).
NO
YES
NO
Go to the next page.
YES
There is a
foreign matter around
the fan.
The
resistance
between the
power wire terminals
of the fan motor and
motor frame (metal
part) is 1 M
Ω
or below.
Remove the power wire
connector from the fan
motor and measure the
resistance between U
and V, V and W, and W
and U phases (
∗
1).
Turn OFF the power and
wait for 10 minutes.
A
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...