Protection Control
Functions and Control
56
6.2
Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient decrease
of low pressure.
Cooling
Heating
Normal Operation
All compressors step: 1
Pe
<
0.15 MPa
(21.8 psi)
Pe
<
0.25 MPa
(36.3 psi)
Pe
>
0.39 MPa
(56.6 psi)
Pe
<
0.07 MPa (10.2 psi)
Pe: Low pressure sensor
detection value for master
unit
Master unit: Compressor step: 1
Slave unit: All stop
Abnormal stop
(
E4
is displayed)
Low pressure standby
(3 times within 60 minutes)
Low pressure standby
(4 times within 60 minutes)
Normal Operation
9-step down
9-step up
3-step up
21-step down
After 10 seconds
After 15 seconds
After 15 seconds
After 10 seconds
Pe < 0.07 MPa
(10.2 psi)
Pe < 0.04 MPa
(5.8 psi)
Pe > 0.12 MPa
(17.4 psi)
Pe > 0.09 MPa
(13.1 psi)
Pe < 0.07 MPa
(10.2 psi)
Pe < 0.06 MPa
(8.7 psi)
Compressor step: 1
After 10 seconds
Upper limit compressor step: max (Max. Step)
Pe < 0.03 MPa
(4.35 psi)
Pe: Low pressure sensor
detection value for each
outdoor unit
Current step
maintained
Abnormal stop
(
E4
is displayed)
Low pressure standby
(3 times within 60 minutes)
Low pressure standby
(4 times within 60 minutes)
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...