SiUS341802E
Field Settings from Remote Controller
Field Settings and Test Operation
94
1.2
Wireless Remote Controller
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
To change the field settings, proceed as follows:
1. Press the
INSPECTION/TEST
button for 4 seconds during normal mode to enter the field setting mode.
2. Press the
MODE
button to select the desired mode No.
3. Press the
UP
button to select the first code No.
4. Press the
DOWN
button to select the second code No.
5. Press the
RESERVE
button to confirm the setting.
6. Press the
INSPECTION/TEST
button to return to the normal mode.
RESERVE
button
INSPECTION/TEST
button
Mode No.
Field setting mode
UP
button
DOWN
button
First code No.
Second code No.
MODE
button