Troubleshooting by Error Code
SiUS341802E
171
Service Diagnosis
Note:
Check the drain piping for
clogging or upward slope, etc.
Replace the indoor unit main
PCB (A1P).
Replace the drain pump (M1P)
or check for dirt, etc.
YES
YES
NO
NO
The drain
pump works when
the power supply is reset for
the indoor unit.
The
voltage
of drain pump
terminals (
∗
2) is in
accordance to the
criteria (
∗
3) (within 5
minutes of resetting
the power
supply).
A
Model
∗
1: Float switch (S1L) /
short circuit connector
∗
2: Drain pump (M1P)
connector
∗
3: Drain pump (M1P)
voltage
FXFQ-T
X15A
X10A
13 VDC
FXFQ-P
X15A
X25A
220-240 VAC
FXZQ-TA
X15A
X102A
13 VDC
FXZQ-M
X8A
X25A
220-240 VAC
FXUQ-P
X15A
X25A
13 VDC
FXEQ-P
X15A
X25A
13 VDC
FXDQ-M
X8A
X25A
220-240 VAC
FXSQ-TA
X15A
X25A
13 VDC
FXMQ-PB
X15A
X25A
220-240 VAC