Troubleshooting by Error Code
SiUS341802E
247
Service Diagnosis
2.52 Power Supply Voltage Imbalance
Error Code
P1
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect voltage imbalance through PCB.
Error Decision
Conditions
When power supply voltage imbalance exceeds approximately 12 V.
Error is not decided while the unit operation is continued.
P1
will be displayed by pressing the inspection button.
Supposed
Causes
Open phase
Interphase voltage imbalance
Defective capacitor in the main circuit
Defective inverter PCB
Defective magnetic relay
Defective wiring in the main circuit