SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
272
Note:
∗
NO
YES
YES
The
number of indoor
units connected to the
same system is not
more than 64.
Incorrect
electric heater
capacity setting
troubleshooting (
∗
1)
checked?
Replace the outdoor unit main
PCB (A1P).
Replace the outdoor unit main
PCB (A1P).
Refer to Incorrect electric heater
capacity setting troubleshooting.
(
∗
1)
Excess indoor units are
connected.
Check for the connection to
connect the proper number of
indoor units.
NO
Diagnosis Flowchart-1
UA-17
Error code
Sub code
NO
Is the
model of indoor
unit FXTQ?
YES
NO
YES
Check if the
refrigerant type of
the outdoor unit
corresponds to that
of the indoor
unit.
Replace the outdoor unit main
PCB (A1P).
Match the refrigerant types of the
outdoor unit and the indoor unit.
Diagnosis Flowchart-2
Error code
Sub code
UA-18