SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
276
2.66 Incorrect Electric Heater Capacity Setting
Error Code
UA-17
Applicable
Models
FXTQ-TA
Outline
After attaching optional electric heater, if the electric heater capacity setting (11(21)-5) is made
mistakenly for heaters not featured in the lineup, heating via unintended levels of airflow will be
prevented.
However, the electric heater will be operable for convenience.
Error Decision
Conditions
Checks when the capacity setting (11(21)-5) of the electric heater has been set to a non-applicable
value.
Operation After
Error Codes
Decided
The error code
UA-17
is displayed on the remote controller.
Indoor units can operate continuously.
Incorrect setting is kept.
Even if the ON condition for electric heater 2 is established, only electric heater 1 will be set to
ON.
(Electric heater 1 set to ON, electric heater 2 set to OFF)
(In order to deliver in terms of user-friendliness and safety, the electric heater can operate at the
lowest possible power levels.)
The airflow of the fan during operation of the electric heater will be set to the largest value within
the CFM dictated by the capacity of each of the electric heaters (electric heater 1, electric heater
2 both set to ON).
All other operations are the same as during normal operation.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...