Field Setting from Outdoor Unit
SiUS341802E
139
Field Settings and Test Operation
B. When the Normal demand operation is carried out. (Use of the external control adaptor for outdoor
unit is not required.)
1. While in setting mode 2, set the item 2-32 (Setting of alternate demand) to ON.
2. While in setting mode 2, select a demand 1 level for the item 2-30.
Image of operation in the case of A
Image of operation in the case of B
P
F1
F2
N
X1M
Host computer monitor panel or demand controller
If carrying out demand or low-noise input, connect the terminals
of the external control adaptor for outdoor unit as shown below.
To other external control adaptor
for outdoor unit
Outside
wiring
indicated by
dotted line.
1
2
3
C
Demand
Low
noise
Power consumption
Rated
40 %
Forced thermostat OFF
(Fan operation)
70 %
Demand level 1
instructing
Power consumption set by
Demand 1 level setting
.
Demand level 2
instructing
Demand level 3
instructing
The power
consumption
during the
demand level 1
instructing can be
set with the
Demand 1 level
setting
.
(70 % of rated
power
consumption has
been set at
factory.)
The power consumption set with
Demand 1 level setting
.
When the
Normal demand
setting
is set to
ON (
OFF
has
been set at
factory.), the
power
consumption can
be set with the
Demand 1 level
setting
. (70 % of
rated power
consumption has
been set at
factory.)
Power consumption
Rated
70 %
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...