Troubleshooting by Error Code
SiUS341802E
201
Service Diagnosis
Troubleshooting
Note:
∗
1. Connector
Diagnosis procedure 2
Infrared floor sensor error
(Error code
CE-02
)
Turn off the power and then reconnect.
Check infrared floor sensor output; refer to sensor
and address data No. 26.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection of
the connector on
infrared floor sensor PCB
(A3P) and the connector
(
∗
1) on A2P
normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
"--" by the above
verification
method.
Normal.
NO
Displays
CE-02
again or "--" for
sensor and
address data.
Replace the sensor.
Model
Connector for infrared floor sensor PCB
FXFQ-T
X2A
FXUQ-P
X81A