Field Settings from Remote Controller
SiUS341802E
101
Field Settings and Test Operation
Filter Cleaning Sign
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
∗
Filter cleaning sign is not displayed when an Auto-clean Panel is connected.
Time for Absence Area Detection
(For units with an infrared presence/floor sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to the energy-
saving end by 1°C (maximum 2°C) after the state of absence continues for a certain period of time.
Absent time defined for detection can be selected as follows:
• The set temperature displayed on the remote controller remains same even if the target temperature is shifted.
• As soon as people is detected while the temperature is shifted, this control will be cancelled (reset).
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Mode No.
First Code No.
Second Code No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
30 (60)
∗
60 (120)
∗
31
19
28
27
26
17
21
30
29
20
18
Elapsed time of absence (min.)
Set temperature (˚C)
Human detection
Cooling (at 28˚C)
Heating (at 20˚C)
State of absence
∗
The values in parentheses represent the time
when Second code No. is "02."
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...