Protection Control
SiUS341802E
59
Functions and Control
Radiation fin temperature control
Perform the following control of integrated as well as multi units for each inverter compressor.
Condition
RXLQ72TATJU
RXLQ72TAYDU
RXLQ72TAYCU
RXYQ72/96/120TAYCU
A
more than 95°C (203°F)
more than 96°C (204.8°F)
more than 90°C (194°F)
B
less than 92°C (197.6°F)
less than 93°C (199.4°F)
less than 87°C (188.6°F)
C
more than 100°C (212°F)
more than 100°C (212°F)
more than 95°C (203°F)
Condition
RXLQ96/120TATJU
RXLQ96/120TAYDU
RXLQ96/120TAYCU
RXYQ144/168TAYCU
A
more than 70°C (158°F)
more than 70°C (158°F)
more than 90°C (194°F)
B
less than 67°C (152.6°F)
less than 67°C (152.6°F)
less than 87°C (188.6°F)
C
more than 75°C (167°F)
more than 75°C (167°F)
more than 95°C (203°F)
Normal operation
Fin temperature standby
Reduce compressor capacity
When occurring 4 times within 60
minutes, the error code
L4
is output.
A
B
C