Field Setting from Outdoor Unit
SiUS341802E
115
Field Settings and Test Operation
2.1.2 When Mounting a Spare PCB
Caution:
After replacement with spare PCB, be sure to make settings shown in the table on the following page.
The procedure for making settings of spare PCB is different from that used for factory settings described
above. Be sure to refer to the table shown on the following page in order to make settings of spare PCB after
replacement.
Enforce a re-initialization of communication: hold press button BS3 “RETURN” for minimum 5 seconds.
After initialization, a test operation is required from outdoor unit (hold BS2 “SET” till indication
t01
appears).
(3) BS button (BS1~BS3)
(2) Segment display (SEG1~SEG3)
(4)
DIP switch
(DS1-1~4)
(DS2-1~4)
(1)
Microcomputer
normal monitor
(HAP)
Connection terminal
for transmission use
ON
OFF
1 2 3 4
DS1
ON
OFF 1 2 3 4
DS2
Initial position
of DIP switches
Position
Set switch
(1) Microcomputer normal monitor
This monitor blinks while in normal operation, and turns ON or OFF when an error occurs.
(2) 7 segment display
· Used to check the transmission.
· Used to display the transmission state between indoor and outdoor units.
· Used to display the contents of error.
· Used to display the contents of field setting.
(3) BS button
Used to change mode.
(4) DIP switch
Used to make field settings.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...