Field Settings from Remote Controller
SiUS341802E
95
Field Settings and Test Operation
1.3
Simplified Remote Controller
1. Remove the upper part of remote controller.
2. When in the normal mode, press the
BS6
button (2) (field setting) to enter the field setting mode.
3. Select the desired MODE No. with the
BS2
button (3) (temperature setting
V
) and the
BS3
button (3)
(temperature setting
W
).
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been selected), press
the
BS8
(4) button (unit No.) and select the indoor unit No. to be set. (This operation is unnecessary when
setting by group.)
5. Press the
BS9
button (5) (set A) and select first code No.
6. Press the
BS10
button (6) (set B) and select second code No.
7. Press the
BS7
button (7) (set/cancel) once and the present settings are confirmed.
8. Press the
BS6
button (8) (field setting) to return to the normal mode.
Mode No.
Unit No.
First code
No.
Second
code No.
(3)
(3)
(2)(8)
(7) (4) (5) (6)