SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
174
Notes:
∗
1: Check the following connectors.
∗
2. Resistance measuring points and judgment criteria.
Model
Connector
FXFQ-T
X20A, Relay connector
FXFQ09-30P
X20A, Relay connector
FXFQ36/48P
X20A
FXZQ-TA
X20A, Relay connector
FXUQ-A
X20A, Relay connector
FXEQ-P
X20A
FXSQ05-48TA
X8A
FXMQ07-12PB
X8A
FXAQ-P
X20A
Measuring point
FG-GND
Vsp-GND
Vcc-GND
Vdc-GND
Criteria
1 M
Ω
or more
100 k
Ω
or more
100
Ω
or more
100 k
Ω
or more
Judgment criteria
1 White
2 Orange
3 Brown
4 Blue
5 —
6 Red
FG
Vsp
Vcc
GND
—
Vdc
1 White
2 Orange
3 Brown
4 Blue
5 —
6 —
7 Red
FG
Vsp
Vcc
GND
—
—
Vdc
—
PG
Vsp
Vcc
GND
—
—
Vm
1 —
2 White
3 Orange
4 Brown
5 Blue
6 —
7 —
8 Red
{
{
{
{ {
{
{
{
1
—
2
—
3
FG
4
Vsp
5
Vcc
Vdc
1
GND
2
—
3
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...