Troubleshooting by Error Code
SiUS341802E
207
Service Diagnosis
2.28 Missing of Ground Leakage Detection Core
Error Code
E2
Applicable
Models
All outdoor unit models
Method of Error
Detection
Error is detected according to whether or not there is continuity across the connector X101A
for leakage detection circuit (Q1LD).
Error Decision
Conditions
No current flows at the time of turning ON the power supply.
Supposed
Causes
Disconnection of connector X101A
Wiring disconnection
Defective outdoor unit main PCB
Troubleshooting
Sub code: 06-08
NO
YES
YES
Is the system reset to
normal?
Is X101A connected?
The error is considered to have
resulted from external factors
other than failures (e.g. noise).
Turn OFF the power supply, and
then disconnect compressor leads.
YES
Properly connect the connector.
NO
Confirm if there is
a leakage with a Megger
tester.
Replace the outdoor unit main
PCB (A1P).
NO
Replace the compressor (M1C).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Ensure the unit
corresponding to the error
code
E2
in monitor mode.
E02-06: Master
E02-07: Slave 1
E02-08: Slave 2
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...