SiUS341802E
Field Setting from Outdoor Unit
Field Settings and Test Operation
128
When operation parameters return to normal range, the capacity priority is switched OFF, enable to
reduce airflow rate depending on night-time low noise operation is still required (end time for night-time
low noise operation is not reached or external input night-time low noise operation is still closed).
[2-30]: Power consumption limitation level (step 1) via the external control adaptor (DTA104A61/62)
If the system needs to be running under power consumption limitation conditions when an external
signal is sent to the unit, this setting defines the level power consumption limitation that will be applied
for step 1. The level is according to the table.
[2-31]: Power consumption limitation level (step 2) via the external control adaptor (DTA104A61/62)
If the system needs to be running under power consumption limitation conditions when an external
signal is sent to the unit, this setting defines the level power consumption limitation that will be applied
for step 2. The level is according to the table.
Value
[2-30]
Power consumption limitation
(approximately)
1
60%
2
65%
3 (default)
70%
4
75%
5
80%
6
85%
7
90%
8
95%
Value
[2-31]
Power consumption limitation
(approximately)
1 (default)
40%
2
50%
3
55%
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low
noise operation start setting
Low noise mode
instructing
operation sound set with
external low noise setting
22:00
20:00
24:00
6:00 7:00 8:00
Set with night-time low noise operation start
setting. (Factory setting is 22:00.)
Set with night-time low noise operation end
setting. (Factory setting is 8:00.)
∗
Operation sound mode
set with night-time low
noise operation setting
∗
Low noise
mode instructing
∗
Operation sound set with
external low noise setting
∗
Night-time
If capacity priority is set in
capacity priority setting, the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with night-time low
noise operation end setting
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...