Field Settings from Remote Controller
Field Settings and Test Operation
92
1. Field Settings from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of installation or after
service inspection / repair, make the field setting in accordance with the following description.
Wrong setting may cause error.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be required to change.
Refer to information in the option handbook.)
1.1
Wired Remote Controller
1.1.1 BRC1E73
<Basic screen>
(1)
<Service Settings menu screen>
(2)
Press Menu/OK button.
<Service Settings screen>
(3)
(4)
(5)
(3)
(5)
Press Menu/OK button.
FIRST CODE (SW) NO.
SECOND CODE NO.
Press and hold Cancel
button for 4 seconds or
more during backlight lit.
In the case of individual
setting per indoor unit
In the case of group total
setting
1.
Press and hold Cancel button for
4 seconds or more.
Service settings menu is
displayed.
2.
Select
Field Settings
in the
Service Settings menu, and
press Menu/OK button.
Field settings screen is
displayed.
3.
Highlight the mode, and select
desired “Mode No.” by using
(Up/Down) button.
4.
In the case of setting per indoor
unit during group control (When
Mode No. such as
20
,
21
,
22
,
23
,
25
are selected), highlight the
unit No. and select “Indoor unit
No.” to be set by using
(Up/Down) button.
(In the case of group total setting,
this operation is not needed.)
In the case of individual setting
per indoor unit, current settings
are displayed. And, SECOND
CODE NO. “ - ” means no
function.
5.
Highlight SECOND CODE NO. of
the FIRST CODE NO. to be
changed, and select desired
“SECOND CODE NO.” by using
(Up/Down) button. Multiple
identical mode number settings
are available.
In case of setting for all indoor
units in the remote control
group, available SECOND
CODE NO. is displayed as “
∗
”
which means it can be
changed.
When SECOND CODE NO. is
displayed as “ - ”, there is no
function.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...