Field Setting from Outdoor Unit
SiUS341802E
131
Field Settings and Test Operation
Automatic lockout
When this setting is made, the auto-backup function will automatically be activated. This will allow the
auxiliary or secondary heat source to be automatically energized in the event of a system failure related
to outdoor units.
Error codes capable of auto-backup are listed in the table below. Please be aware that the error codes
that are not listed do not auto-backup in order to protect the unit.
Error code
(Auto backup
possible)
Error contents
A3
Drain level control system abnormality
E3
Actuation of high pressure switch
E4
Actuation of low pressure sensor
E5
Inverter compressor motor lock
E6
Compressor damage alarm
E7
Outdoor fan motor abnormality
E9
Electronic expansion valve coil abnormality
F3
Discharge pipe temperature abnormality
F4
Wet alarm
H3
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H7
Outdoor fan PCB abnormality
H9
Outdoor air thermistor (R1T) abnormality
J3
Discharge pipe thermistor (R21T) abnormality, Compressor body thermistor (R14T) abnormality
J5
Compressor suction thermistor (R12T) abnormality, Suction pipe thermistor (R10T) abnormality
J6
Heat exchanger deicer thermistor (R11T) abnormality
Heat exchanger gas pipe thermistor (R8T, R9T) abnormality
J7
Receiver inlet thermistor (R3T) abnormality
Subcooling heat exchanger liquid pipe thermistor (R7T) abnormality
Subcooling injection thermistor (R16T) abnormality
J8
Heat exchanger liquid pipe thermistor (R4T, R5T) abnormality
Leak detection thermistor (R15T) abnormality
J9
Subcooling heat exchanger gas pipe thermistor (R6T) abnormality
Receiver gas purge thermistor (R13T) abnormality
JA
High pressure sensor abnormality
JC
Low pressure sensor abnormality
L1
Inverter PCB abnormality
L2
Momentary power failure during test operation
L3
Reactor temperature rise abnormality
L4
Inverter radiation fin temperature rise abnormality
L5
Inverter compressor instantaneous overcurrent
L8
Inverter compressor overcurrent
L9
Inverter compressor startup abnormality
LC
Transmission error between inverter PCB and outdoor unit main PCB
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...