Troubleshooting by Error Code
Service Diagnosis
214
Note:
∗
1. Make a comparison between voltage measured by the pressure sensor and that read by the
pressure gauge.
(The pressure sensor makes measurement of voltage at its connector block to convert it to
pressure.
)
NO
YES
Are
the high
pressure and
low pressure checked
by the service checker the
same as the actual measured
values of the high and
low pressure
sensors?
Replace the outdoor unit main
PCB (A1P).
NO
Replace the inverter PCB.
RXLQ-TATJU,
RXLQ-TAYDU: A3P
RXLQ-TAYCU,
RXYQ-TAYCU: A4P
CHECK 4
Is the power transistor
normal?
YES
Replace the compressor.
A
CHECK 12
CHECK 4
CHECK 12