Troubleshooting by Error Code
SiUS341802E
243
Service Diagnosis
2.50 Inverter Compressor Startup Abnormality
Error Code
L9
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect error according to the signal waveform of compressor.
Error Decision
Conditions
When compressor startup operation has not been completed.
Supposed
Causes
The stop valve is not opened
Defective compressor
Error in wire connections to compressor
Large differential pressure before compressor startup
Defective inverter PCB
Troubleshooting
YES
NO
NO
Apply power, and then restart
operation.
NO
Are the
leads of the
compressor
disconnected?
Connect the leads of the compressor.
YES
Is the
insulation
resistance of the relevant
compressor 100 k
Ω
or more?
Eliminate the melting state of
refrigerant.
NO
YES
YES
YES
Refrigerant is
melting (No power
applied for a period of 6
hours or more)
Eliminate the melting state of
refrigerant.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the stop valve
open?
Startup for
the first time after
installation?
Is a proper
amount of refrigerant
charged?
Open the stop valve.
NO
Charge a proper amount of
refrigerant.
Go to the next page.
NO
A
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...