SiUS341802E
Field Settings from Remote Controller
Field Settings and Test Operation
96
1.4
List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(
∗
2)
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
10(20)
0
Filter sign setting
(Setting for display time to
clean air filter)
(Sets display time to clean air
filter to half when there is
heavy filter contamination.)
Ultra long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
—
—
Long life filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
1
Ultra long life filter sign setting
Long life filter
Ultra long life filter
—
—
1 (
∗
7) Filter cleaning sign time (Light/Heavy)
2,500/1,250
10,000/5,000
—
—
2
Selection of thermistor
Remote cont
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
—
2 (
∗
6) Remote sensor and remote controller thermistor
—
Only remote sensor
Only remote
controller
thermistor
—
3
Filter cleaning sign
Displayed
Not displayed
—
—
6
Remote controller thermostat control during the
group control
Remote controller
thermostat control
is not permitted
Remote controller
thermostat control
is permitted
—
—
7 (
∗
9) Time for absence area detection
30 minutes
60 minutes
—
—
11(21)
1
Auxiliary electric heater ON temperature: Ton
Refer to page 102 for details.
2
Auxiliary electric heater OFF temperature: Toff
3
Setting the airflow rate when heating
Standard
Slightly increased
Increased
—
3 (
∗
6) Electric heater setting
Refer to page 103 for details.
5 (
∗
6) Electric heater capacity setting
Refer to page 103 for details.
6 (
∗
9) Setting the rate of human detection
High sensitivity
Low sensitivity
Standard
sensitivity
Infrared
presence/floor
sensor
disabled
7
Airflow adjustment
OFF
Completion of
airflow adjustment
Start of airflow
adjustment
—
8 (
∗
9) Compensating the temperature around people
Suction air
temperature only
Priorities given on
the suction air
temperature
Standard
Priorities given
on the floor
temperature
9 (
∗
9) Compensating the floor temperature
–4°C (–7.2°F)
–2°C (–3.6°F)
0°C (0°F)
+2°C (+3.6°F)
12(22)
0
Optional output switching
(field selection of output for adaptor for wiring)
Refer to page 105 for details.
1
External ON/OFF input
(Set when ON/OFF is to be controlled from
outside.)
Refer to page 105 for details.
2
Thermostat switching
(Set when remote sensor is to be used)
1°C (1.8°F)
0.5°C (0.9°F)
—
—
3
Airflow setting when heating thermostat is OFF
LL tap
Set fan speed
OFF (
∗
8)
—
4
Setting of operation mode to AUTO
(automatic temperature differential setting for
VRV
system Heat Pump series cool/heat)
Refer to page 106 for details.
5
Auto restart after power failure reset
Not equipped
Equipped
—
—
6
Airflow setting when cooling thermostat is OFF
LL tap
Set fan speed
OFF (
∗
8)
—
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...