SiUS341802E
Field Settings from Remote Controller
Field Settings and Test Operation
102
Auxiliary Electric Heater ON/OFF Temperature
Note:
∗
1.
S
value varies automatically based on the room temperature trend.
FXFQ-T, FXMQ-PB
FXUQ-P, FXEQ-P, FXLQ-M, FXNQ-M, FXTQ-TA
There is a limitation of combination between Ton and Toff as below due to 2°C (3.6°F) hysteresis required for
reliability.
z
: Available
— : Not available
Set temperature
Toff +
S
(
∗
1)
Ton +
S
(
∗
1)
Thermostat
OFF
Thermostat
ON
Mode No.
First Code No.
Symbol
Second Code No.
01
02
03
04
05
06
11 (21)
1
Ton
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
Toff
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–1°C
(–1.8°F)
–0.5°C
(–0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
Mode No.
First Code No.
Symbol
Second Code No.
01
02
03
04
05
06
11 (21)
1
Ton
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
2
Toff
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
–1°C
(–1.8°F)
–0.5°C
(–0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
Second Code No.
Ton
01
02
03
04
05
06
–4°C
(–7.2°F)
–3.5°C
(–6.3°F)
–3°C
(–5.4°F)
–2.5°C
(–4.5°F)
–2°C
(–3.6°F)
–1.5°C
(–2.7°F)
Tof
f
06
0.5°C (0.9°F)
z
z
z
z
z
z
05
0°C (0°F)
z
z
z
z
z
—
04
–0.5°C (–0.9°F)
z
z
z
z
—
—
03
–1°C (–1.8°F)
z
z
z
—
—
—
02
–1.5°C (–2.7°F)
z
z
—
—
—
—
01
–2°C (–3.6°F)
z
—
—
—
—
—
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...