TECHNICAL GUIDE

SINGLE PIECE ECM
AIR HANDLERS

FOR USE WITH SPLIT-SYSTEM
AIR CONDITIONERS & HEAT PUMPS

MODELS: AHV18 THRU 60 

Due to continuous product improvement, 
specifications are subject to change without notice.

Visit us on the web at:

www.york.com

Additional rating information can be found at:

www.ahridirectory.org

WARRANTY

Standard 5-year limited parts warranty.

Extended 10-year limited parts warranty when product is
registered online within 90 days of purchase for replace-
ment or closing for new home construction.

ISO 9001

Certified Quality

Management System

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

824755-YTG-C-0912

DESCRIPTION

The AHV Air Handler line offers the ultimate in comfort, sound
and application flexibility. The air handler is shipped ready to be
installed in upflow, horizontal left or right position, with minor
adjustments. No special kits are required to install this deluxe
product.

Air handlers are shipped with “Flex-coils” without a factory
installed metering device. Flex coil models allow these coils to
be used with R-22 or R-410A for added flexibility to meet refrig-
erant choices. An orifice metering device or a R-410A TXV
should be installed in the field to meet your system require-
ments. 

FEATURES

Thermostatic Expansion Valve

 - Provides the ultimate refrig-

erant control required for today’s high efficient product. The
UPG bolt-on TXV provides easy installation to convert the air
handler to the required refrigerant, which is a true bolt-on
design that does not require brazing to replace or install.

Rust-proof Plastic Drain Pans - 

The vertical and horizontal

drain pans in these units are made of a fiberglass reinforced
thermoset polymer that will not rust or compromise stability at
high temperatures.

Insulated Cabinet

 - All air handler cabinets are thermally insu-

lated with 3/4” foil faced insulation to prevent sweating.

Factory Sealed -

 Achieves 2% or less total airflow leakage rate

at duct leakage test conditions for system airflow verification.

Durable Finish Inside and Out

 - Air handler casings are made

of pre-painted galvanized steel which provides a better paint to
steel bond that resists corrosion and rust creep. All internal coil
sheet metal parts are made of G60 galvanized or prepainted
G30 galvanized steel.

Filters - 

All models have internal filter racks provided for use

with 1” thick standard size filters.

Electric Heat Kits - 

The 6HK series of field installed electric

heat kits are available for installation friendly and easy service
applications. These 6HK kits have heat capacities from 2 kW to
25 kW to meet the application requirements.

ECM Variable Speed Motor -

 Designed for efficient, quiet oper-

ation with added indoor comfort control. With the use of a
humidistat, the system will monitor the humidity in the home
and automatically keep the desired humidity level in both winter
and summer seasons. The ECM motor utilizes only 24% of the
energy used by standard blower motors to reduce your overall
heating and cooling costs.

The climate

 

comfort system allows dealer to customize comfort

settings based on regional location.

Communications

 - These models may be connected as part of

a communications system using a 4-wire connection bus.

Summary of Contents for AHV18B

Page 1: ... that does not require brazing to replace or install Rust proof Plastic Drain Pans The vertical and horizontal drain pans in these units are made of a fiberglass reinforced thermoset polymer that will not rust or compromise stability at high temperatures Insulated Cabinet All air handler cabinets are thermally insu lated with 3 4 foil faced insulation to prevent sweating Factory Sealed Achieves 2 ...

Page 2: ... 17 13 32 20 AHV42D AHV48D AHV60D 57 24 1 2 26 20 29 32 23 1 2 7 8 1 All dimensions are in inches 2 Actual size conduit size COIL TECHNICAL DATA Models Application Refrig Conn Types Face Area Sq Ft Rows Deep Fins Per In Coil Size Tube Geometry Tube Dia Fin Type AHV18B3XH21 Cooling Heat Pump Sweat 3 4 2 14 2 14 x 17 5 1 x 0 866 3 8 Enhanced AHV24B3XH21 Cooling Heat Pump Sweat 3 9 3 12 2 16 x 17 5 1...

Page 3: ...5 6 37 8 80 67 52 3 44 6 36 9 28 4 75 62 42 2 35 2 26 8 19 3 70 57 33 6 29 6 25 4 21 4 AHV30B 585 85 72 38 7 34 4 30 1 24 7 80 67 33 6 28 9 23 9 18 9 75 62 27 2 22 7 17 8 12 8 70 57 21 2 18 6 16 2 13 7 795 85 72 50 8 45 2 38 4 32 0 80 67 43 7 36 8 31 24 0 75 62 35 7 29 5 23 1 16 1 70 57 27 9 24 5 21 17 6 985 85 72 64 9 54 45 6 37 8 80 67 52 3 44 6 36 9 28 4 75 62 42 2 35 2 26 8 19 3 70 57 33 6 29 ...

Page 4: ...7 45 2 41 35 4 29 7 1600 85 72 102 2 90 74 3 60 4 80 67 83 6 70 6 57 2 43 1 75 62 66 1 54 41 2 27 0 70 57 50 7 46 1 39 8 33 4 AHV60D 1190 85 72 83 6 73 7 62 9 51 6 80 67 68 2 58 4 48 4 37 1 75 62 54 9 45 3 34 8 23 9 70 57 42 2 37 3 31 9 26 9 1390 85 72 95 9 84 1 71 9 58 8 80 67 79 2 67 4 54 4 41 6 75 62 62 4 51 2 39 7 26 9 70 57 48 42 5 36 8 30 6 1565 85 72 106 3 94 2 78 5 63 5 80 67 87 6 73 9 60 ...

Page 5: ...OP2 Minimum Wire Size AWG 3 208V 230V 208V 230V 18B 24B 30B 2 7 2 3 3 4 2 9 15 14 36C 42D 3 6 3 2 4 5 4 0 15 14 48D 60D 5 3 4 9 6 6 6 1 15 14 1 FLA Full Load Amps 2 MOP Maximum Overcurrent Protection device must be HACR type circuit breaker or time delay fuse 3 75 C copper wire only If wire other than non plated 75 C ambient copper wire is used consult applicable tables of the NEC and local codes ...

Page 6: ...06 14 4 10 8 13 2 36 9 45 1 3 6 4 4 10 8 13 2 6HK 1 2 6501806 17 3 13 0 15 9 44 3 54 2 6 5 7 9 13 0 15 9 6HK 1 2 6502006 19 2 14 4 17 6 49 2 60 2 7 2 8 8 14 4 17 6 6HK 1 2 6502506 24 0 18 0 22 0 61 5 75 2 7 2 8 8 18 0 22 0 3PH 6HK06501025 9 6 7 2 8 8 24 6 30 1 7 2 8 8 7 2 8 8 6HK06501525 14 4 10 8 13 2 36 9 45 1 10 8 13 2 10 8 13 2 6HK06501825 17 3 13 0 15 9 44 3 54 2 13 0 15 9 13 0 15 9 6HK165020...

Page 7: ...90 100 3 3 6HK 1 2 6502006 80 0 91 2 104 0 100 110 3 3 AHV48D 6HK 0 1 6500206 10 0 17 5 18 6 20 20 12 12 6HK 0 1 6500506 20 0 28 3 31 1 30 35 10 8 6HK 0 1 6500806 32 0 41 3 46 1 45 50 8 8 6HK 0 1 6501006 40 0 50 0 56 1 50 60 8 6 6HK 1 2 6501306 52 0 63 0 71 1 70 80 6 4 6HK 1 2 6501506 60 0 71 6 81 1 80 90 4 4 6HK 1 2 6501806 72 0 84 6 96 1 90 100 4 3 6HK 1 2 6502006 80 0 93 3 106 1 100 110 3 2 AHV...

Page 8: ...ype circuit breaker or time delay fuse 2 Stated sizes are for 75 C copper wire only If wire other than non plated 75 C ambient copper wire is used consult applicable tables of the NEC and local codes 3 1st Circuit includes the blower motor amps ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Heater Amps 240V Field Wiring Min Circuit Ampacity MOP1 Min Wi...

Page 9: ...I SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Total Heater Amps 240V Min Circuit Ampacity MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Circuit 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd AHV36C AHV42D 6HK16502025 46 2 29 5 25 0 32 9 28 9 30 25 35 30 10 10 8 10 AHV48D 6HK16502025 46 2 31 7 25 0 35 0 28 9 35 25 35 30 8 10 8 10 AHV60D 6HK16502...

Page 10: ...ontrol board 3 For heat pump applications set AC HP jumper on air handler control board to the HP position AIR HANDLER WITH COMMUNICATING AC OR HP Air Handler Control Wiring Typical A C Cooling only Applications THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM COM HUMIDISTAT THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R R G Y W1 W2 C G W1 W2...

Page 11: ...00 715 1150 750 1365 890 C C 1080 702 1170 761 1305 846 D C 990 644 1035 675 1229 801 High Low Speed Heat CFM Heat Tap ADJ Tap2 AHV18 AHV24 AHV30 AHV36 High Low High Low High Low High Low A Any 850 650 1100 740 1100 740 1360 900 B Any 700 600 960 650 960 650 1150 770 C Any 550 550 830 600 830 600 1000 630 D Any 400 400 580 550 580 550 720 550 Heat Tap ADJ Tap2 AHV42 AHV48 AHV60 High Low High Low H...

Page 12: ...THE AIR HANDLER HEATER KIT COMBINATION ON THIS UNIT S INSTALLATION INSTRUCTIONS HEATER KITS 6HK 6500206 6HK 6500506 HEATER KITS 6HK 6500806 6HK 6501006 HEATER KITS 6HK16501306 6HK16501506 HEATER KITS 6HK16501806 6HK16502006 HEATER KIT 6HK16502506 24V 240V COM 208V XFORMER HE1 LS FL HE2 LS FL HE3 LS FL HE4 LS FL HE5 LS FL SEQ or RLY SEQ SEQ SEQ SEQ or RLY RED GRN BLU WHT BRN USE COPPER CONDUCTORS O...

Page 13: ...ODES GND EQUIPMENT GROUND FL FUSIBLE LINK HE HEATING ELEMENT LS LIMIT SWITCH REL RELAY FIELD POWER WIRING 208 230V FACTORY WIRING 208 230V FACTORY WIRING LOW VOLTAGE L1 L2 L3 L1 L2 L3 GND GND GND GND L1 L2 L3 L1 L2 L3 REL1 REL2 REL3 REL4 REL5 REL6 HE1 HE6 HE5 HE4 HE3 HE2 FL FL FL FL FL FL REL1 REL2 REL3 HE1 HE3 HE2 FL FL FL REL1 REL2 REL3 REL4 REL5 REL6 HE1 HE6 HE5 HE4 HE3 HE2 FL FL FL FL FL FL ...

Page 14: ...o change without notice Published in U S A 824755 YTG C 0912 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 824755 YTG B 0612 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: