Johnson Controls Unitary Products
824755-YTG-C-0912
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
Air
Handlers
Models
Heater
Models
Total
Heater
Amps
@240
V
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V
230V
208V
230V
208V
230V
Circuit
Circuit
Circuit
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
AHV24B
AHV30B
6HK16501306
52.0
22.2 37.6
–
24.6 43.3
–
25
40
–
25
45
–
10
8
–
10
8
–
6HK16501506
60.0
25.1 43.3
–
27.9 50.0
–
30
45
–
30
50
–
10
8
–
10
8
–
AHV36C
AHV42D
6HK16501306
52.0
23.3 37.6
–
25.7 43.3
–
25
40
–
30
45
–
10
8
–
10
8
–
6HK16501506
60.0
26.2 43.3
–
29.0 50.0
–
30
45
–
30
50
–
10
8
–
10
8
–
6HK16501806
72.0
43.5 39.0
–
49.0 45.0
–
45
40
–
50
45
–
8
8
–
8
8
–
6HK16502006
80.0
47.8 43.3
–
54.0 50.0
–
50
45
–
60
50
–
8
8
–
6
8
–
AHV48D
6HK16501306
52.0
25.4 37.6
–
27.8 43.3
–
30
40
–
30
45
–
10
8
–
10
8
–
6HK16501506
60.0
28.3 43.3
–
31.1 50.0
–
30
45
–
35
50
–
10
8
–
8
8
–
6HK16501806
72.0
45.6 39.0
–
51.1 45.0
–
50
40
–
60
45
–
8
8
–
6
8
–
6HK16502006
80.0
49.9 43.3
–
56.1 50.0
–
50
45
–
60
50
–
8
8
–
6
8
–
AHV60D
6HK16501306
52.0
25.4 37.6
–
27.8 43.3
–
30
40
–
30
45
–
10
8
–
10
8
–
6HK16501506
60.0
28.3 43.3
–
31.1 50.0
–
30
45
–
35
50
–
10
8
–
8
8
–
6HK16501806
72.0
45.6 39.0
–
51.1 45.0
–
50
40
–
60
45
–
8
8
–
6
8
–
6HK16502006
80.0
49.9 43.3
–
56.1 50.0
–
50
45
–
60
50
–
8
8
–
6
8
–
6HK16502506
100.0
49.9 43.3 21.7 56.1 50.0 25.0
50
45
25
60
50
25
8
8
10
6
8
10
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY - 208/230-3-60
Air Handler Models
Heater
Models
Heater
Amps
@ 240V
Field Wiring
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V
230V
208V
230V
208V
230V
AHV24B
AHV30B
6HK06501025
23.1
28.4
31.8
30
35
10
8
6HK06501525
34.6
40.9
46.1
45
50
8
8
AHV36C
AHV42D
6HK06501025
23.1
29.5
32.9
30
35
10
8
6HK06501525
34.6
42.0
47.3
45
50
8
8
6HK06501825
41.6
49.6
56.0
50
60
8
6
6HK16502025
3
46.2
54.6
61.8
60
70
6
6
AHV48D
6HK06501025
23.1
31.7
35.0
35
35
8
8
6HK06501525
34.6
44.1
49.4
45
50
8
8
6HK06501825
41.6
51.7
58.1
60
60
6
6
6HK16502025
3
46.2
56.7
63.9
60
70
6
6
AHV60D
6HK06501025
23.1
31.7
35.0
35
35
8
8
6HK06501525
34.6
44.1
49.4
45
50
8
8
6HK06501825
41.6
51.7
58.1
60
60
6
6
6HK16502025
3
46.2
56.7
63.9
60
70
6
6
6HK16502525
3
57.7
69.1
78.3
70
80
4
4
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes..
3. The 20kW and 25kW heater models (6HK16502025 and 6HK16502525) come with circuit breakers standard. Single source power MCA and MOP requirements are
given here only for reference if used with field installed single point power modification.