background image

Johnson Controls Unitary Products

5

824755-YTG-C-0912

PHYSICAL & ELECTRICAL DATA - COOLING ONLY

 MODELS

Models

18B

24B

30B

36C

42D

48D

60D

Blower - Diameter x Width

10 x 8

10 x 8

10 x 8

11 x 10

11 x 10

11 x 10

11 x 10

Motor

HP

1/3 HP

1/3 HP

1/3 HP

1/2 HP

1/2 HP

3/4 HP

3/4 HP

Nominal RPM

1050

1050

1050

1050

1050

1050

1050

Voltage

208/230

208/230

208/230

208/230

208/230

208/230

208/230

Full Load Amps @230V

2.3

2.3

2.3

3.2

3.2

4.9

4.9

Filter 

1

Type

DISPOSABLE OR PERMANENT

Size

16 x 20 x 1

16 x 20 x 1

16 x 20 x 1

20 x 20 x 1

22 x 20 x 1

22 x 20 x 1

22 x 20 x 1

Permanent Type Kit

1PF0601BK

1PF0601BK

1PF0601BK

1PF0602BK

1PF0603BK

1PF0603BK

1PF0603BK

Shipping / 
Operating Weight (lbs.)

116/104

121/106

121/106

153/138

169/151

172/154

175/157

1.  Field supplied.

KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT

For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by
the conversion factor in the following table.

DISTRIBUTION POWER

NOMINAL VOLTAGE

CONVERSION FACTOR

208V

240V

0.75

220V

240V

0.84

230V

240V

0.92

ELECTRICAL DATA - COOLING ONLY

Models

Motor FLA

1

Minimum Circuit Ampacity

MOP

2

Minimum Wire 

Size (AWG)

3

208V

230V

208V

230V

18B
24B
30B

2.7

2.3

3.4

2.9

15

14

36C
42D

3.6

3.2

4.5

4.0

15

14

48D
60D

5.3

4.9

6.6

6.1

15

14

1. FLA = Full Load Amps.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75

C, copper wire only.  If wire other than non-plated, 75

C ambient, copper wire is used, consult applicable tables of the NEC and local codes..

ELECTRICAL HEAT: MINIMUM FAN SPEED

1

Heater Kit Models

2,3

Nom. kW

@240V

Air Handler Models

AHV18B

AHV24B

AHV30B

AHV36C

AHV42D

AHV48D

AHV60D

6HK(0,1)6500206

2.4kW

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

6HK(0,1)6500506

4.8kW

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

6HK(0,1)6500806

7.7kW

Med-Low (C)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

6HK(0,1)6501006

6HK06501025

9.6kW

Med-Low (C)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

Low (D)

6HK(1,2)6501306

12.5kW

-

Med-Low (C) Med-Low (C)

Low (D)

Low (D)

Low (D)

Low (D)

6HK(1,2)6501506

6HK06501525

14.4kW

-

Med-Low (C) Med-Low (C) Med-Low (C)

Low (D)

Low (D)

Low (D)

6HK(1,2)6501806

6HK06501825

17.3kW

-

-

-

Med-Low (C) Med-Low (C)

Low (D)

Low (D)

6HK(1,2)6502006

6HK16502025

19.2kW

-

-

-

Med-High (B) Med-High (B)

Low (D)

Low (D)

6HK(1,2)6502506

6HK16502525

24kW

-

-

-

-

-

-

Low  (D)

1. The referenced letter in this table is for the heat jumper tap.
2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
3. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.

Summary of Contents for AHV18B

Page 1: ... that does not require brazing to replace or install Rust proof Plastic Drain Pans The vertical and horizontal drain pans in these units are made of a fiberglass reinforced thermoset polymer that will not rust or compromise stability at high temperatures Insulated Cabinet All air handler cabinets are thermally insu lated with 3 4 foil faced insulation to prevent sweating Factory Sealed Achieves 2 ...

Page 2: ... 17 13 32 20 AHV42D AHV48D AHV60D 57 24 1 2 26 20 29 32 23 1 2 7 8 1 All dimensions are in inches 2 Actual size conduit size COIL TECHNICAL DATA Models Application Refrig Conn Types Face Area Sq Ft Rows Deep Fins Per In Coil Size Tube Geometry Tube Dia Fin Type AHV18B3XH21 Cooling Heat Pump Sweat 3 4 2 14 2 14 x 17 5 1 x 0 866 3 8 Enhanced AHV24B3XH21 Cooling Heat Pump Sweat 3 9 3 12 2 16 x 17 5 1...

Page 3: ...5 6 37 8 80 67 52 3 44 6 36 9 28 4 75 62 42 2 35 2 26 8 19 3 70 57 33 6 29 6 25 4 21 4 AHV30B 585 85 72 38 7 34 4 30 1 24 7 80 67 33 6 28 9 23 9 18 9 75 62 27 2 22 7 17 8 12 8 70 57 21 2 18 6 16 2 13 7 795 85 72 50 8 45 2 38 4 32 0 80 67 43 7 36 8 31 24 0 75 62 35 7 29 5 23 1 16 1 70 57 27 9 24 5 21 17 6 985 85 72 64 9 54 45 6 37 8 80 67 52 3 44 6 36 9 28 4 75 62 42 2 35 2 26 8 19 3 70 57 33 6 29 ...

Page 4: ...7 45 2 41 35 4 29 7 1600 85 72 102 2 90 74 3 60 4 80 67 83 6 70 6 57 2 43 1 75 62 66 1 54 41 2 27 0 70 57 50 7 46 1 39 8 33 4 AHV60D 1190 85 72 83 6 73 7 62 9 51 6 80 67 68 2 58 4 48 4 37 1 75 62 54 9 45 3 34 8 23 9 70 57 42 2 37 3 31 9 26 9 1390 85 72 95 9 84 1 71 9 58 8 80 67 79 2 67 4 54 4 41 6 75 62 62 4 51 2 39 7 26 9 70 57 48 42 5 36 8 30 6 1565 85 72 106 3 94 2 78 5 63 5 80 67 87 6 73 9 60 ...

Page 5: ...OP2 Minimum Wire Size AWG 3 208V 230V 208V 230V 18B 24B 30B 2 7 2 3 3 4 2 9 15 14 36C 42D 3 6 3 2 4 5 4 0 15 14 48D 60D 5 3 4 9 6 6 6 1 15 14 1 FLA Full Load Amps 2 MOP Maximum Overcurrent Protection device must be HACR type circuit breaker or time delay fuse 3 75 C copper wire only If wire other than non plated 75 C ambient copper wire is used consult applicable tables of the NEC and local codes ...

Page 6: ...06 14 4 10 8 13 2 36 9 45 1 3 6 4 4 10 8 13 2 6HK 1 2 6501806 17 3 13 0 15 9 44 3 54 2 6 5 7 9 13 0 15 9 6HK 1 2 6502006 19 2 14 4 17 6 49 2 60 2 7 2 8 8 14 4 17 6 6HK 1 2 6502506 24 0 18 0 22 0 61 5 75 2 7 2 8 8 18 0 22 0 3PH 6HK06501025 9 6 7 2 8 8 24 6 30 1 7 2 8 8 7 2 8 8 6HK06501525 14 4 10 8 13 2 36 9 45 1 10 8 13 2 10 8 13 2 6HK06501825 17 3 13 0 15 9 44 3 54 2 13 0 15 9 13 0 15 9 6HK165020...

Page 7: ...90 100 3 3 6HK 1 2 6502006 80 0 91 2 104 0 100 110 3 3 AHV48D 6HK 0 1 6500206 10 0 17 5 18 6 20 20 12 12 6HK 0 1 6500506 20 0 28 3 31 1 30 35 10 8 6HK 0 1 6500806 32 0 41 3 46 1 45 50 8 8 6HK 0 1 6501006 40 0 50 0 56 1 50 60 8 6 6HK 1 2 6501306 52 0 63 0 71 1 70 80 6 4 6HK 1 2 6501506 60 0 71 6 81 1 80 90 4 4 6HK 1 2 6501806 72 0 84 6 96 1 90 100 4 3 6HK 1 2 6502006 80 0 93 3 106 1 100 110 3 2 AHV...

Page 8: ...ype circuit breaker or time delay fuse 2 Stated sizes are for 75 C copper wire only If wire other than non plated 75 C ambient copper wire is used consult applicable tables of the NEC and local codes 3 1st Circuit includes the blower motor amps ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Heater Amps 240V Field Wiring Min Circuit Ampacity MOP1 Min Wi...

Page 9: ...I SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Total Heater Amps 240V Min Circuit Ampacity MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Circuit 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd AHV36C AHV42D 6HK16502025 46 2 29 5 25 0 32 9 28 9 30 25 35 30 10 10 8 10 AHV48D 6HK16502025 46 2 31 7 25 0 35 0 28 9 35 25 35 30 8 10 8 10 AHV60D 6HK16502...

Page 10: ...ontrol board 3 For heat pump applications set AC HP jumper on air handler control board to the HP position AIR HANDLER WITH COMMUNICATING AC OR HP Air Handler Control Wiring Typical A C Cooling only Applications THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R R G Y W1 W2 C G W1 W2 Y C Y Y2 Y1 O HUM COM HUMIDISTAT THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R R G Y W1 W2 C G W1 W2...

Page 11: ...00 715 1150 750 1365 890 C C 1080 702 1170 761 1305 846 D C 990 644 1035 675 1229 801 High Low Speed Heat CFM Heat Tap ADJ Tap2 AHV18 AHV24 AHV30 AHV36 High Low High Low High Low High Low A Any 850 650 1100 740 1100 740 1360 900 B Any 700 600 960 650 960 650 1150 770 C Any 550 550 830 600 830 600 1000 630 D Any 400 400 580 550 580 550 720 550 Heat Tap ADJ Tap2 AHV42 AHV48 AHV60 High Low High Low H...

Page 12: ...THE AIR HANDLER HEATER KIT COMBINATION ON THIS UNIT S INSTALLATION INSTRUCTIONS HEATER KITS 6HK 6500206 6HK 6500506 HEATER KITS 6HK 6500806 6HK 6501006 HEATER KITS 6HK16501306 6HK16501506 HEATER KITS 6HK16501806 6HK16502006 HEATER KIT 6HK16502506 24V 240V COM 208V XFORMER HE1 LS FL HE2 LS FL HE3 LS FL HE4 LS FL HE5 LS FL SEQ or RLY SEQ SEQ SEQ SEQ or RLY RED GRN BLU WHT BRN USE COPPER CONDUCTORS O...

Page 13: ...ODES GND EQUIPMENT GROUND FL FUSIBLE LINK HE HEATING ELEMENT LS LIMIT SWITCH REL RELAY FIELD POWER WIRING 208 230V FACTORY WIRING 208 230V FACTORY WIRING LOW VOLTAGE L1 L2 L3 L1 L2 L3 GND GND GND GND L1 L2 L3 L1 L2 L3 REL1 REL2 REL3 REL4 REL5 REL6 HE1 HE6 HE5 HE4 HE3 HE2 FL FL FL FL FL FL REL1 REL2 REL3 HE1 HE3 HE2 FL FL FL REL1 REL2 REL3 REL4 REL5 REL6 HE1 HE6 HE5 HE4 HE3 HE2 FL FL FL FL FL FL ...

Page 14: ...o change without notice Published in U S A 824755 YTG C 0912 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 824755 YTG B 0612 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: