Troubleshooting by Error Code
SiUS341802E
167
Service Diagnosis
2. Troubleshooting by Error Code
2.1
External Protection Device Abnormality
2.1.1 External Protection Device Abnormality (All Indoor Unit Models)
Error Code
A0
Applicable
Models
All indoor unit models
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Supposed
Causes
Actuation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
ON/OFF
input from
outside (mode No.
12, first code No. 1) has
been set to external protection
device input (second
code No. 03) by
remote
controller.
Check the setting state of the
external ON/OFF input by
remote controller.
Ex
ternal
protection device
is connected to T1 and T2
of the indoor unit
terminal.
Replace the indoor unit main
PCB (A1P).
Actuation of external protection
device.
Change the second code No. to
01
or
02
.
YES
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...