SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
238
2.47.3 Inverter Radiation Fin Temperature Rise Abnormality (Diode Bridge)
Error Code
L4
Sub code: 12-14
Applicable
Models
RXLQ96/120TATJU, RXLQ96/120TAYDU
Method of Error
Detection
Diode bridge radiation fin temperature is detected by the thermistor.
Error Decision
Conditions
Detected temperature exceeds a certain level.
Supposed
Causes
Insulation sheet (blue) improperly fixed on the heat sink
Radiation fin plate not fixed with screws
U0
error
Defective diode bridge
High outdoor air temperature
Troubleshooting
Turn ON the
power supply, and
check if the error recurs
when operation
starts.
Turn ON the
power supply, and
check if the error recurs
when operation
starts.
Troubleshooting is finished.
Replace the diode bridge (V1R).
If the problem recurs, replace the
inverter PCB (A3P).
YES
Continue operation.
Field factor. Radiation fin temperature
may have risen due to high outdoor
temperature.
NO
Rectify troubles.
NO
Disconnect, and then
reconnect the connector
(X8A) for the fin thermistor on
the inverter PCB (A3P).
Normal?
YES
Replace the thermistor (R72T).
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...