SiUS341802E
Field Setting from Outdoor Unit
Field Settings and Test Operation
140
Image of operation in the case of A and B
Detailed Setting Procedure of Night-time Low Noise Operation and Demand Control
1. Setting mode 1 (H1P OFF)
In setting mode 2, press the BS1 (MODE button) once
→
Setting mode 1 is entered and H1P turns OFF.
While the setting mode 1 is displayed,
In night-time low noise operation
and
In demand control
are
displayed.
2. Setting mode 2 (H1P ON)
(1) In setting 1, press and hold the BS1 (MODE button) for more than 5 seconds.
→
Setting mode 2 is entered
and H1P lights.
(2) Press the BS2 (SET button) several times and match the LED display with the Setting No. you want.
(3) Press the BS3 (RETURN button) once, and the present setting content is displayed.
→
Press the BS2 (SET button) several times and match the LED display with the setting content you want.
(4) Press the BS3 (RETURN button) two times.
→
Returns to (1).
(5) Press the BS1 (MODE button) once
→
Returns to the setting mode 1 and H1P turns OFF.
The power consumption set with
Demand 1 level setting
.
Demand level
2 instructing
Demand level
3 instructing
The power
consumption can
be set with the
Demand 1 level
setting
. (70 % of
rated power
consumption has
been set at
factory.)
During continuous
demand operation, when
the external demand
instruction is received
repeatedly, the instruction
with higher demand level
has the precedence.
Power consumption
Rated
Forced thermostat OFF
(Fan operation)
40 %
70 %
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...